| Applications | HVAC applications, building, museums, libraries |
| Main features | Digital interface for electronic recording and digital control
Integrated Sensor
Calculates dewpoint / frost point
With or without display
Probe extensions available |
| Probe type | Integrated, Airchchip3000 Type |
| Humidity sensor | ROTRONIC Hygromer ® IN1 |
| Temperature sensor | Pt100 1/3 Class B |
| Long term stability | < 1 %rh/Year |
| Measuring range with integrated probe | 0…100 %rh / -100…150 °C |
| Calibration / adjustment | via Rotronic HW4 Software |
| Accuracy w. adjustment profile "standard" | Yes, factory certificate |
| Accuracy at 23 ±5 °C | ±0,8 %rh / ±0.2 K |
| Response time t 63 | <10 s for 63% of a leap 35> 80% RH (1m/sec airflow at the sensor) |
| Backlight | Yes |
| Engineering units displayed | 1 or 2 decimal places |
| Keypad (with display only) | Yes |
| Exploitation software | Software HW4 |
| Trend indicator | Yes, on models with display |
| Probe adjustment by software | With HW4 Software & Sevice cable |
| Psychrometric calculations | Dew or frost point |
| Event logging | Systemic Events (FDA, GAMP) |
| Aim value input by | as a simulator for system validation |
| Firmware update | Via Internet / Software HW4 |
| User information | from HW4 Device manager |
| Data processing via HW4 | Interfacecable |
| Audit Trail/ electronic records | FDA 21 CFR Part 11, GMP compliant |
| Power supply / Power consumption | 15…40 VDC, 12…28 VAC or 230 VAC |
| Digital output signal (standard) | Mini USB to UART |
| Communication interfaces | USB, RS485 or Ethernet TCP/IP |
| Service Interface | Mini USB |
| Max. able length service cable | 5 m |
| Probe material | Polycarbonate |
| Enclosure material | ABS |
| Cable connections | 1x M16x1.5 or ½“ Conduit Adapter |
| Weight | approx. 300 g |
| IP protection rating | IP20 |
| Fire protection class | Meets UL94-HB |
| FDA/GAMP compatibility | FDA CFR21 Part 11 and GAMP |