Applications
Measures relative humidity and temperature and calculates all psychrometric parameters in the fi elds of HVAC, industry and pharmaceuticals.
Features
• Interchangeable HC2 probes
• Accuracy: see chapter «Probes»
• Temperature limit at probe: see chapter «Probes»
• Range of application electronics: -40…60 °C / 0…100 %rh; -10…60 °C with LCD
• Digital outputs, also combinable with analog outputs
• Use as simulator for system validation *
• Service interface
| Dimensions | HF52, HF53, HF54, HF55: 129 x 72 x 45 mm HF56: 192 x 102 x 52 mm |
|---|---|
| Operating range electronics | -40…60 °C / -10…60 °C (Models with display) 0…100 %rh, non-condensing |
| Accuracy at 23 ±5 °C | Probe dependent |
| Measuring range with interchangeable probe | 0…100 %rh and -50…200 °C |
| Power supply / Power consumption | 15…40 VDC or 12…28 VAC/ <100 mA |
| Psychrometric calculations | All psychrometric values |
| Number of probe inputs | 1 |
| Initialisation time | Typically <3 sec. |
| Display type | Optional graphics display. Presentation configurable. |
| Backlight | with Backlight |
| Alerting | Sensor break or short circuit, programmable. |
| Alarm indicators | Yes |
| Exploitation software | ROTRONIC HW4 |
| Trend indicator | Yes, for models with display |
| Probe adjustment by software | Yes, with service cable |
| Probe adjustment by keypad | display / keyboard |
| Remote control functions | Via HygroPalm and service cable |
| Firmware update | With internet or HW4 software |
| Data processing via HW4 | Graphics, statistics, analysis, qualification, etc. |
| Circuit type | 2 -Wire or 3/4-Wire |
| Analogue outputs scaleable by the user | Yes |
| Analog output signal (standard) | 2 x 0…1 V, 0…5 V, 0…10 V, 0(4)…20 mA |
| Automatic load compensation | Yes |
| Communication interfaces | RS-458 / USB / LAN / WLAN / PoE (Modus B) |
| Service Interface | Mini USB (UART) |
| Service Information | Calibration interval |
| Max. nr. of devices in RS485 network | 64 |
| Max. cable length service cable | 5 m |
| Max. probe cable length | 10 m |
| Enclosure material | ABS |
| Cable connections | M16 cable gland and screw terminals |
| IP protection rating | IP63 (except models with USB / Ethernet interface) |
| Fire protection class | Complies UL94-HB |
| Weight | 220 g / 500 g |
| FDA/GAMP compatibility | FDA 21 CFR Part 11 and GAMP compatible |